TM 55-2210-224-12
Table 4-2. Unit Troubleshooting (continued)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
ENGINE (cont)
9.
ENGINE STOPS WHILE IN OPERATION. (cont)
Step 3.
Check for air in fuel lines.
Bleed and prime fuel system. Refer to TM 5-2815-233-14.
Step 4.
Check for improper operation of fuel pump.
Refer to TM 5-2815-233-14.
Step 5.
Check for any control switch having accidentally been switched to OFF position.
Set control switch to ON.
Step 6.
Check for EMER SHUTDOWN switch in STOP position.
Set EMER SHUTDOWN switch to RUN.
LUBRICATION SYSTEM
10.
LOW LUBE OIL PRESSURE.
Step 1.
Check for improper lube oil level.
Refer to LO 55-2210-224-12.
Step 2.
Check for loose or broken oil line.
Tighten or replace oil line. (TM 5-2815-233-14)
MAIN GENERATOR
11.
MAIN GENERATOR FLASHOVER.
Step 1.
Check for rough or eccentric commutator.
Notify intermediate direct support maintenance.
Step 2.
Check for dirt or foreign particles in insulating spaces between commutator segments.
Notify intermediate direct support maintenance.
4-18