3-19. MULTIPLE-UNIT RECEPTACLE (cont)
CLEANING, INSPECTION, AND REPAIR
WARNING
Dry-cleaning solvent P-D-680 is toxic and flammable. Wear protective goggles and gloves and use only in
a well-ventilated area. Avoid contact with skin, eyes, and clothes and don't breathe vapors. Do not use
near open flame or excessive heat. The flash point is 100-138°F (38-59°C). If you become dizzy, get
fresh air and get medical aid, immediately. If contact with eyes is made, wash your eyes and get medical
aid immediately.
Compressed air used for cleaning purposes will not exceed 30 psi (207 kPa). Do not direct compressed air
against skin. Use goggles or full face shield.
9.
Use a cloth dampened with dry-cleaning solvent and clean parts. Dry with compressed air.
10.
Inspect pins for pitted or burned areas. Replace damaged pins.
11.
Inspect housing for bends or dents. Replace damaged housing.
12.
Inspect for broken or frayed wiring. Replace damaged wires.
13.
Inspect for broken or cracked insulation plates. Replace damaged insulator plates.
TEST
14.
Use a multimeter and perform a continuity test on the multiple-unit receptacle. Replace defective part.
16.
Use a megohmmeter and perform a resistance test on the multiple-unit receptacle. Replace defective part.
ASSEMBLY AND INSTALLATION
16.
Install insulator plate (9), if removed.
17.
Connect wires to pins (8). Remove tags.
18.
Install insulator plate (7).
19.
Position pin assembly (6) on receptacle housing (11) and secure with screws (5).
20.
Install housing cover (4), spring (3), cover hinge shaft (2), and snapring (1).
21.
Install receptacle housing (11) and secure with four bolts (10).